Thank you for your interest in General Electric Company part number TEC36015XL, a Circuitbreaker item that we offer here on Aerospace Materials Supply. This product is listed with the NSN 5925-01-458-0684, and you can obtain customized procurement solutions on this component from our team members by completing and submitting the form below. For our specialists to best deliver quotes that accommodate your specifications, please be sure we are presented with essential details like your target price, desired quantity, and anticipated fulfillment timeline. Once we have the opportunity to receive and review your submission, we will strive to provide a tailored response for your consideration within 15 minutes or less.
Note : We Will Not Share Your Information To Any Third Parties.
Besides part number TEC36015XL, you may browse our platform further for similar components produced by General Electric Company under the CAGECode 60969, as well as additional products that are categorized under FSC 5925 Circuit Breakers. If you have any questions regarding our services or the NSN 5925-01-458-0684 items that we sell, you may always give us a call or email, as we would be delighted to assist you in any way that we can. Otherwise, we encourage you to request a quote for part number TEC36015XL at your earliest convenience.
MRC | Criteria | Characteristic |
---|---|---|
AEBY | Distance Between Centerlines Of Mounting Facilities Parallel To Body Length | 4.875 INCHES NOMINAL |
BBRJ | Special Handling Feature | MAGNETIC |
FEAT | Special Features | XL DESIGNATION AT END OF PART NUMBER INDICATES NO LUGS ARE SUPPLIED |
CPLM | Maximum Continuous Load Current Rating Per Pole | 15.0 AMPERES AC ALL LOCATIONS |
AKPX | Pole Quantity | 3 |
CBBL | Features Provided | ADJUSTABLE TRIP RELEASE |
CPRF | Operating Voltage Type And Rating Per Pole In Volts | 600.0 AC ALL LOCATIONS |
CPRH | Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
CPRJ | Trip Release Method | THERMAL-MAGNETIC ALL LOCATIONS |
AEHA | Distance Between Centerlines Of Mounting Facilities Parallel To Body Width | 1.375 INCHES NOMINAL |
CPRN | Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 130.0 ALL LOCATIONS |
FREQ | Frequency In Hertz | 60.0 ALL LOCATIONS |
CPRL | Trip Release Characteristic | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CPRR | Main Contact Tripping Mechanism Type | TRIP FREE |
CRCF | Trip Release Ambient Temp Rating | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
AJEC | Boss Height | 0.250 INCHES NOMINAL |
AXHR | Mounting Facility Type And Quantity | 4 UNTHREADED HOLE |
CPRX | Actuator Position Designation | AT POLE TWO |
CPRT | Manual Actuator Type And Quantity | 1 TOGGLE |
CPRW | Actuator Function | TRIP-RESET |
ADTV | Case Material | PLASTIC |
ADAT | Body Width | 4.125 INCHES NOMINAL |
BBRG | Storage Type | GENERAL PURPOSE WAREHOUSE |
MRC | Decoded Requirement | Clear Text Reply |
ADAQ | Body Length | 6.312 INCHES NOMINAL |
AEBP | Center To Center Distance Between Terminals Parallel To Length | 5.875 INCHES NOMINAL |
ADAU | Body Height | 3.375 INCHES NOMINAL |
AAQL | Body Style | MULTIPOLE-SINGLE ACTUATOR TYPE |
AEBQ | Center To Center Distance Between Terminals Parallel To Width | 1.375 INCHES NOMINAL |
CPRG | Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 10000.0 AC ALL LOCATIONS |
CQWN | Trip Delay Time In Seconds Per Rated Continuous Current | 120.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
AEBV | Unthreaded Mounting Hole Diameter | 0.203 INCHES NOMINAL |
CPRQ | Reset Method | MANUAL |
CPSF | Adjustable Trip Setting Current Range Per Pole In Amps | +42.0/+198.0 AC ALL LOCATIONS |
CQXF | Inclosure Protection Type For Which Designed | GENERAL PURPOSE AND FUNGUS RESISTANT |